FLUXMASTER 50 INSTRUCTION MANUAL
CONDITION CHECK POINT COUNTERMEASURE
Is the power source voltage delivered to Check if the power source is on.
L1, L2 terminal (is the charging indicator
Turn power source OFF and then ON again.
illuminated)?
Reconfirm the power voltage level.
Motor
Is there voltage output from output Turn power source OFF and then ON again.
terminal T1,T2 and T3?
Inoperative
Is the motor wired correctly? Check motor wiring.
Is there any abnormal condition in the AC drive?
Refer to fault handling
instructions to examine and correct wiring.
Has reverse rotation been disabled? Check parameter F_22
Is the analog frequency setting loaded?
Check to see if wiring for analog
Motor
frequency input signal is correct.
Inoperative
Is the operation mode setting correct?
Check if the frequency input setting
voltage is correct.
Is wiring on the output terminals T1,T2
Correct with motor rotation direction setting
Motor runs in and T3 correct? (Fn_04) or FWD/REV key
opposite direction
Is the wiring for the forward and reverse Wiring should be in accordance with the
signals correct? U,V,W terminals of motor.
Is the wiring for analog frequency input correct?
Examine the wiring and correct it.
Motor run speed
Is the operation mode setting correct? Check the Operation panel.
does not change
Is the loading too heavy? Reduce loading.
Is the specification of motor (poles,
Reconfirm motor specification.
Motor runs
voltage) correct?
at speed too Is the gear ratio correct? Reconfirm gear ratio.
high or too low Is the highest output frequency setting correct? Reconfirm highest output frequency.
Is the voltage on motor side significantly reduced?
Cheek wiring to motor. Check DC bus voltage.
Is the loading too heavy?
Reduce loading variation.
Abnormal speed Is the loading variation too large? Increase AC drive and motor capacity.
variation at operation
Is the input power source steady and stable?
Install AC reactor on the power supply
input side.