FLUXMASTER 50 INSTRUCTION MANUAL
INDICATION CONTENT DESCRIPTION
When speed F_11 = 0, Frequency lower limit F_7 = 0 and frequency setting < 1Hz
SP0 Zero Speed Stopping When speed F_11 = 1, Frequency lower limit F_7 < (F_6/100), and frequency setting
<Frequency upper limit (F_6/100)
1. If the inverter is set to external operation (F_10 = 1) and
direct start is disabled (F_28 =1),the AC drive cannot be started and will flash
SP1 Failure to start directly SP1 when the run command is attempted after applying power
(see descriptions of F_28 power-up start).
2. Direct start is possible when F_28 = 0.
The inverter setup to external operation (F_10 = 1). If the STOP
SP2
Keypad emergency key in the keypad is pressed during operation, the AC drive stops according the
stop stop method F_14 and flashes SP2 after stop.The RUN switch must be turned
OFF then ON to restart the machine.
External emergency
When the external emergency stop signal is activated through
E.S.
stop
the multi-function input terminal, the AC drive decelerates and stops.
E.S. flashes after AC drive stops.(Refer to instruction for F_19 for detail).
When the external BASE BLOCK signal is activated through
b.b. External BASE BLOCK the multi-function terminal, the AC drive stops output immediately
and flashes b.b. for indication.(Refer to instruction for F_19 for detail)
Keypad Operation Error Instruction
INDICATION CONTENT POSSIBLE CAUSE COUNTERMEASURE
1. Attempt to reverse direction 1. Adjust F_22 to 0
LOC Motor direction locked when F_22 reverse disable = 1 2. Adjust F_04 to 0
2. Attempt to set F_22 to 1 when F_04 = 1 (motor rotation direction)
1. Press ▲ or ▼ keys when F_11 = 1
or under SP1 operation 1. Use
▲ or ▼ keys to adjust frequency
Er1 Keypad operation error 2. Attempt to modify F_29 setting only after F_11 = 0
3. Attempt to modify parameter (keypad model)
that is not allowed to be modified 2. Do not modify F_29
during operation 3. Modify in stop mode only
(refer to parameter list)
Er2 Parameter setting error
1. F_6 < F_7 (upper frequency limit<
1. Set F_6 > F_7
lower frequency limit)