F_26: SP2 (1 ~ 200Hz) , Multi-speed 2 (Refer to F_19 / F_20)
F_27: SP3 (1 ~ 200Hz) , Multi-speed 3 (Refer to F_19 / F_20)
F_28: Power Up Start = 0 : Power Up start enabled when remote Run command on
= 1 : Power Up start disabled when remote Run command on
(CPU version V2.1 and above)
When F_28 = 1 and control mode is remote control (F_10 = 1), the AC drive can not start if the RUN switch is ON when power is
engaged.The run signal must be toggled off then on to run the AC drive.
F_29: CPU Program Version
F_30: Fault log for last three faults
1. Last three faults: indicate the sequence of the occurrence of faults by the location of decimal point. x.xx indicates a
recently occurred fault.
xx.x indicates the prior fault event. xxx. Indicates the earliest fault in the record.
2. After entering the F_30 function, the x.xx trip record will be displayed first.After that, press button and you can read activity
in a chronological order.
xx.x xxx. x.xx xxx, consecutively.
3. After entering F_30 function, if the RESET button is pressed, the trip record will be cleared. (Indication display
-.--, --.-, and ---.
results)
4. When the content of trip indicates O.CC,it will indicate the latest trip code is OC-C and so on.
48
FLUXMASTER 50 INSTRUCTION MANUAL