20
15-Group Drive Status and Function Reset
Function
Code No.
Description Range (unit) /Code
Factory
Setting
Communication
Address
Remarks
15-0
Drive Horsepower
Code
--- --- 134 or (0x86) *3
15-1
Software Version
--- --- 135 or(0x87) *3
15-2
Fault Jog
(Last 3 Faults)
--- --- 136 or(0x88) *3
15-3
Accumulated
Operation Time(Hours)
0 - 9999 --- 139 or(0x8B) *3
15-4
Accumulated
Operation Time(Hours
X 10000)
0 - 27 --- 140 or(0x8C) *3
15-5
Accumulated
Operation Time Mode
0: Time Under Power
1: Run Mode Time Only
0000 141 or (0x8D) *3
15-6
Reset Parameter
1110: Reset for 50 Hz Motor
Operation
1111: Reset for 60 Hz Motor
Operation
0000 142 or (0x8E) *1
15-7
Parameter locking
password
0000 ~ 0999 0 228 or (0xE4) *4
15-8
Copy Unit
0000: Disable
0001: Inverter to Copy Unit
0002: Copy Unit to Inverter
0003: Verify
0 42 or (0x2A) *3
15-9
Display of Pressure
Setting
0000: Setting and Feedback
0001: Only Setting
0002: Only Feedback
0 198 or (0xC6) *4
16-Group Operation Parameters
Function
Code No.
Description Range (unit) /Code Factory Setting
Communication
Address
Remarks
16-0
Frequency Upper Limit
(Hz)
0.01 – 400.00 (Hz) 60.00 (Hz) 24 or (0x18) *1
16-1
Frequency Lower Limit
(Hz)
0.00 – 400.00 (Hz) 00.00 (Hz) 25 or (0x19) *1
16-2
Acceleration Time
0.1 – 3600.0 (sec) 5.00 (sec) 26 or (0x1A)
16-3
Deceleration Time
0.1 – 3600.0 (sec) 5.00 (sec) 27 or (0x1B)
16-4
Sleep Deceleration
Time
0.1 – 3600.0 (sec) 3.00 (sec) 31 or (0x1F) *3
16-5
Sleep Frequency
0.00 - 400.00 (Hz) 35.00 (Hz) 155 or (0x9B) *3
16-6
Period of Water Used
Detection
0.0 – 200.0 (sec) 20.0 (sec) 190 or (0xBE) *3
16-7
Acceleration Time of
Water Used Detection
0.1 - 3600.0 (sec) 12.0 (sec) 191 or (0xBF) *3
16-8
Pressure Range of
Water Used Detection
0.00 - 2.50 (Bar) 0.10 (Bar) 193 or (0xC1) *3
16-9
HiP/LoP/1BrE
Protection
Auto Restart Time
0 - 200 (min) 20 (min) 192 or (0xC0) *3
16-A
Direction of water
usage
0 : Upward
1 : Downward
1 244 or (0xF4) *1 *5
16-B
Deceleration time of
water usage detection
0.1 – 3600.0 (sec) 40.0 (sec) 245 or (0xF5) *5