17-Group PID Control parameters
Function
Code No.
Description Range (unit) /Code Factory Setting
Communication
Address
Remarks
17-0
Proportional Gain (P)
0.0 – 10.0 1.0 111 or (0x6F)
17-1
Integration Time (I)
0.0–100.0 (sec) 1.0 (sec) 112 or (0x70)
17-2
Differentiation Time (D)
0.00 – 10.00 (sec) 0.00 (sec) 113 or (0x71)
17-3
Output Filter Time (O)
0.0 – 2.5 (sec) 0.0 (sec) 116 or (0x74)
17-4
Feedback Signal
Offset(F)
0.00 – 10.00 1.00 110 or (0x6E)
17-5
Feedback Signal
Type(F)
0000 : 0~10V
0001 : 4~20mA
1 123 or (0x7B) *1*2
17-6
Feedback Signal
Scan Time(F)
1 – 100 (base on 4ms) 5 (20ms of 5*4ms) 75 or (0x4B)
17-7
Liquid Leakage
Detection Time
0.0 - 10.0 (sec) 0.0 (sec) 177 or (0xB1) *3
17-8
Change Level within
Detection Time
0.01 - 2.50 (Bar) 0.10 (Bar) 178 or (0xB2) *3
17-9
Restart Level for Liquid
Leakage Detection
0.01 - 2.50 (Bar) 0.50 (Bar) 179 or (0xB3) *3
18-Group System Protect parameters
Function
Code No.
Description Range (unit) /Code Factory Setting
Communication
Address
Remarks
18-0
Target Pressure Value
0.10 - 25.50 (Bar) 2.00 (Bar) 168 or (0xA8) *3
18-1
Max. Pressure limit
0.10 - 25.50 (Bar) 5.00 (Bar) 166 or (0xA6) *3
18-2
Min. Pressure limit
0.10 - 25.50 (Bar) 0.50 (Bar) 167 or (0xA5) *3
18-3
High Pressure Alarm
Time
0.0 - 600.0 (sec) 10.0 (sec) 169 or (0xA9)
18-4
High Pressure Stop
Time
0.0 - 600.0 (sec) 20.0 (sec) 170 or (0xAA)
18-5
Low Pressure Alarm
Time
0.0 - 600.0 (sec) 10.0 (sec) 171 or (0xAB)
18-6
Low Pressure
Stop Time
0.0 - 600.0 (sec) 20.0 (sec) 195 or (0xC3)
18-7
Sleep Delay Time
0.0 - 120.0 (sec) 0.0 (sec) 162 or (0xA2) *3
18-8
Sleep Tolerance Range
0.00 – 5.00 (Bar) 0.50 (Bar) 165 or (0xA5) *3
18-9
HiP/LoP/1BrE
Protection
Auto Restart Times
0 ~ 999 999 199 or (0xC7) *4
18-A
Pressure losing
prevention level (%)
0 - 100 (rate) 0 (rate) 229 or (0xE5) *5
18-B
Detection time of
pressure losing
0.0 – 25.0 (sec) 0.0 (sec) 239 or (0xEF) *5
18-C
Forced operating
frequency
0.0 – 200.0 (Hz) 0.0 (Hz) 240 or (0xF0) *5