22
19-Group Dual Pumps Parameters
Function
Code No.
Description Range (unit) /Code Factory Setting
Communication
Address
Remarks
19-0
Single/Dual Pump
and
Master/Slave Selection
0 : Single
1 : Dual – Master
2 : Dual – Slave 1
3 : Dual – Slave 2
4 : Dual – Slave 3
0 172 or (0xAC) *3
19-1
Max. Pressure of
Pressure Transmitter
0.10 – 25.50 (Bar) 10.00 (Bar) 173 or (0xAD) *3
19-2
Dual pump synchronal
setting
0 : Disable
1 : Target Pressure Value &
Run/Stop
2 : Only Target Pressure
Value
3 : Only
Run/Stop
0 243 or (0xF3) *5
19-3
Auto Shift Time
0 – 240 (Hour) 1 (Hour) 175 or (0xAF)
19-4
Launch Delay Time
(Slave Unit)
0 – 30.0 (Sec) 10.0 (Sec) 176 or (0xB0)
19-5
AI2 (S6)Gain(%)
0 – 200 (%) 100 (%) 76 or (0x4C)
19-6
Start Frequency for
Slave Pump Running
(100% = 16-0)
0 - 100 (%) 0 (%) 196 or(0xC4) *3
19-7
Start Frequency for
Slave Pump Stopping
(100% = 16-0)
0 - 100 (%) 0 (%) 197 or(0xC5) *3