29
(11):16-5 Sleep Frequency 0.00 – 400.00 Hz
16-6 Period of Water Used Detection 0.0 – 200.0 sec
16-7 Acceleration Time of Water Used Detection 0.1 – 3600.0 sec
16-8 Pressure Range of Water Used Detection 0.00 – 2.50 Bar
16-A Direction of water usage 0 : Upward 1 : Downward
16-B Deceleration time of water usage detection 0.1 – 3600.0 (sec)
16-6 = 0.0 (sec) : Disable water used detection.
When this function is operated, it can reduce the time that pump get into sleep mode
effectively.
When using water frequently, we suggest that set 16-6 (Cycle of water usage
detection) longer to reduce detection times, this would be helpful for lessening
unstable pressure which cause by water usage detection function.
When upward water usage detection is operating, the pressure will slightly increase, if
users do care about the situation, we suggest you can adjust 16-8 (Pressure range of
water usage detection) lower. In other hand, it will extend the time of getting to sleep
when we are not using water or using small amount of water.