28
(10):16-2 Acceleration time 0.1 – 3600.0 sec
16-3 Deceleration time 0.1 – 3600.0 sec
16-4 Sleep deceleration time 0.1 – 3600.0 sec
When|(18-0 Target Pressure Value) – (S6 or AI2 Pressure Feedback) | < 18-8
Sleep Tolerance Range, and Output Frequency is less than 16-5 Sleep Frequency, and
the time is longer than 18-7 Sleep delay time, PID Sleep starts.
When inverter sleep mode starts, deceleration time depends on setting value of 16-4.
Acceleration and deceleration is controlled by parameters 16-2 and 16-3 when using
PID control.
10.0 Bar
18-0 Target Pressure Value
S6 or AI2
Pressure
Feedback
Output Frequency
16-3
Deceleration
16-2
Accelerat
ion
16-2
Acceleration
16-4
Sleep
Decel
0.1 Ba
PID Sleep Start