35
17-7 = 0.0(sec) : Disable Liquid Leakage Detection.
When pump is sleeping, the pressure value maybe decrease because liquid leakage,
if the change of pressure value is lower than 17-8 during every 17-7 detection time,
the pump will keep in sleep mode, until the pressure value is higher than the setting of
17-9 (restart level).
Setting the value of 17-7/17-8/17-9 properly can improve the pump restart condition
due to the liquid leakage.
Water leakage detection function only enable in single pump application.