36
(17):18-0 Target Pressure Value 0.10 – 25.50Bar
18-1 Max. Pressure limit 0.10 – 25.50 Bar
18-2 Min. Pressure limit 0.10 – 25.50 Bar
When using PID control, system pressure will intervene (18-1 Max. Pressure limit) and
(18-2 Min. Pressure limit).
(18):18-0 Target Pressure Value 0.10 – 25.50Bar
18-3 High pressure alarm time 0.0 – 600.0 sec
18-4 High pressure stop time 0.0 – 600.0 sec
Ba
18-1: Max. Pressure limit
Time
Ba
AI2/S6 Feedback signal
time
time
Hz
Hip
Hi-p
T1 T2
T3
AI2/S6 Feedback signal
18-1 Max. Pressure limit
18-0 Target Pressure Value
18-2 Min. Pressure limit
18-0 Target Pressure Value
18-2 Min. Pressure limit
High pressure deceleration time depend by
the (16-3 deceleration time) setting.
T1 < (18-3 High Pressure Alarm Time), the Hip accumulate time will be reset after T1.
T2 = (18-3 High Pressure Alarm Time), Counting high pressure time again and keypad blink Hip.
T3 = (18-4 High Pressure Stop Time), keypad blink Hi-p and deceleration to stop.