37
(19):18-5 Low pressure alarm time 0.0 – 600.0 sec
18-6 Time ow pressure stop time 0.0 – 600.0 sec
(20):18-7 Sleep Delay Time 0.0 – 120.0 sec
18-8 Sleep Tolerance Range 0.00 – 5.00 Bar
AI2/S6 Feedback signal
time
time
Ba
r
Hz
Lop
Lo-p
T1
T2
T3
18-1 Max. Pressure limit
18-0 Target Pressure Value
18-2 Min. Pressure limit
T1 < (18-5 Low Pressure Alarm Time); the Lop accumulate time will be reset after T1.
T2 = (18-5 Low Pressure Alarm Time); Counting low pressure time again and keypad blink Lop.
T3 = (18-6 Low Pressure Stop Time); keypad blink Lo-p and deceleration to stop.
Low pressure deceleration time depend by
the (16-3 deceleration time) setting.