38
Notes: Sleep function can save energy when pressure reached target pressure value.
(21):18-9 HiP/LoP/1BrE Protection Auto Restart Times 0 – 999
1.) 18-9=0: Amount of auto restart is infinite.
2.) 18-9=1~999: When amount of auto restart is over 18-9 setting, then inverter never
restart, until re-power-on or using reset function.
(22): 18-A Pressure losing prevention level (%) 0 – 100 rate
18-B Detection time of pressure losing 0.0 – 25.0 (sec)
1.) When 18-A = 0: Disable.
2.) When 18-A > 0: If Pressure feedback is less than (Pressure setting (18-0) x
Pressure losing prevention level (18-A)) and exceed the detection time (18-B), the
pump will stop and show “PbL”
(23): 18-C Forced operating frequency 0.00 – 200.0 (Hz)
When S1~S5 any DI setting = 6(PID disable), pump will not operate according to PID
function, then set another DI = 7(Forced operating frequency), now the pump will
operate depending on 18-C (Forced operating frequency), and pump stops if remove
the DI(S1~S5=7). This function is use for when pressure sensor is offline or breakdown.
(24):19-0 Single/Dual Pump and Master/Slave Selection 0000: Single
0001: Dual – Master
0002: Dual – Slave 1
0003: Dual – Slave 2
0004: Dual – Slave 3
19-2 Dual pump synchronal setting 0: Disable
1: Target Pressure Value & Run/Stop
2: Only Target Pressure Value
3: Only Run/Stop
19-3 Auto Shift Time 0 – 240 hour
19-4 Launch Delay Time (Slave Unit) 0 – 30.0 sec
19-0 Single/Dual Pump and Master/Slave Selection,
0000: Single 0001: Dual – Master 0002: Dual – Slave
When select dual pump control method (19-0=1, 2), set one inverter 19-0 to “1” another
to “2”.