How to alter parameters
Step 4
RUN using remote speed reference. (Potentiometer 0-10vdc or 4 -
20ma )
1) To run. Activate the remote run switch connected to terminals
S1 ( FWD) or S2 ( REV) as required. Parameter 00-02 = 1
The frequency will ramp up to the frequency set by one of the
following selections according to the set acceleration ramp time:-
Potentiometer on the keypad Parameter 00-05 = 1
External voltage input AVI. Parameter 00-05 = 2
External current input ACI. Parameter 00-05 = 3
2) To Stop. De-activate the remote run switch.
The frequency will ramp down to zero and according to the decel ramp
time.
How to alter parameters using the keypad
1) To alter parameters:- Press the MODE key,
until the first parameter 00-00 is displayed.
2) Then use the arrow keys </ENT
to select the parameter required
then
Press and hold the </ENT until the preset value is displayed
3) Use the and </ENT keys to alter the setting of the parameters as
per basic quick start parameter list.
Note:- For full parameter list refer to the instruction manual.
4) To save each parameter change, press and hold the </ENT until
the word END is displayed.
5) Use </ENT key to select the next parameter to alter and
follow steps 2 to 4 until all changes are complete.
6) Pressing the MODE key repeatedly will alternate the display
between the preset frequency ( flashing display) and the last parameter
accessed or other selectable displays 0 to 7 when selected by parameter
12-00 according to the table below.
0:Disable display 1:Output Current
2:Output Voltage 3:DC voltage
4:Temperature 5:PID feedback
6:AVI 7:ACI