Basic Quick Start Parameter List
Parameter
Default
Range
Note
00-14
10.0
0.1~3600.0
Acceleration time in Secs
00-15
10.0
0.1~3600.0
Deceleration time in Secs
00-04
0
0-2
0: Forward/Stop-Reverse/Stop
1: Run/Stop-Reverse/Forward
2: 3-Wire Control Mode-Run/Stop
00-12
50/60Hz
0.01~650.00
Max frequency limit.
00-13
0.0
0.00~649.00
Min frequency limit
00-02
0
0-2
Start mode:-
0: Keypad
1: Remote
2: Communication
00-05
0
0-6
0: Keypad
1: Potentiometer on keypad
2: External AVI analogue signal
3: External ACI analogue signal
4: External up/down frequency control
5: Control by Communication method
6: PID output
07-09
0
0-1
Stop method:-
0: Decel to stop
1: Coast to stop
02-01
**A
**A
Motor overload protection
13-08
00000
Set to factory setting.
1250: 50HZ system.
1360: 60HZ system.
Note:- For Full Parameter List see the Instruction manual