45 
 
 
 
3.Manual Reset and Auto-Reset Operative Malfunction 
INDICATION CONTENT  POSSIBLE CAUSE  COUNTERMEASURE 
 
 
Transient 
over-current 
starting machine 
 
 
1. Motor coil short-circuit with 
external casing 
2. Motor  connection  wire 
short-circuit with grounding
3. Transistor  module 
damaged 
 
 
1. Examining  motor 
2. Examining  wiring 
3. Replace  transistor  module 
 
 
 
Over-current at 
acceleration 
 
 
1. Acceleration  time  setting 
too short 
2. Improper V/F feature 
selection 
 3. Applied motor capacity 
exceeds inverter capacity 
 
 
1. Adjust acceleration time to 
longer setting  
2. Adjust to a proper V/F curve 
3. Replace and install another 
inverter with appropriate 
capacity 
 
 
Over-current at 
steady speed 
 
 
1. Transient  alteration  of  the 
loading 
2. Transient  alteration  of  the 
power supply 
 
 
1. Examining  the  loading 
configuration 
2. Install inductor on the power 
supply input side 
 
 
 
 
 
Over-current at 
deceleration 
 
 
Deceleration setting too short
 
 
Adjust to use a longer 
acceleration time 
 
 
 
Over-current at 
breaking 
 
 
DC Breaking frequency, 
breaking voltage, or breaking 
time setting too long 
 
 
Adjust to reduce settings of 
F_15, F_16, or F_17 
 
 
 
Over-voltage at 
operation/deceler
ation 
 
 
1. Deceleration time setting 
too short or inertial 
loading too large 
2. Power  supply  voltage 
variation too large 
 
 
1. Adjust  to  use  a  longer 
deceleration time 
2. Install a inductor on the power 
supply input side 
3. Increase  the  capacity  of 
inverter 
 
 
 
Insufficient 
voltage level at 
operation 
 
1. Power  supply  voltage  too 
low 
2. Power  supply  voltage 
variation too large 
 
1. Improve power source quality 
2. Adjust  to  use  a  longer 
acceleration time 
3. Increase capacity of inverter 
4. Install a reactor on the power 
supply input side 
 
 
 
 
Heat-sink over 
heated at 
operation 
 
1. Loading  too  heavy 
2. Ambient  temperature  too 
high or poor ventilation 
 
1. Examining the loading  
2. Increase capacity of inverter 
3. Improve  ventilation 
 
 
OCS 
OCA 
OCC 
OCd 
OCb 
OVC 
LVC 
OHC