46 
 
 
 
Special Condition Description 
INDICATION CONTENT  DESCRIPTION 
 
Zero Speed 
Stopping 
 
When F_11 = 0, F_7= 0 and frequency setting < 1 Hz 
When F_11 = 1, F_7<(F_6/100), and frequency setting 
<(F_6/100) 
 
 
 
 
Fail to start 
directly 
 
1.   If the inverter is set to external operation (F_10 = 1) and 
direct start is disabled (F_28 =1), the inverter cannot be 
started and will flash SP1 when operation switch turned to 
ON after applying power (see descriptions of F_28). 
2.  Direct start is possible when F_28 = 0. 
 
 
Keypad 
emergency stop 
 
The inverter setup to external operation (F_10=1). If the STOP 
key in the keypad is pressed at the middle of operation, the 
inverter stops according the setting in F_14 and flash SP2 after 
stop. The RUN switch must be turned OFF than ON to restart 
the machine. 
 
 
 
External 
emergency stop 
 
When the external emergency stop signal is activated through 
the multi-function input terminal, the inverter decelerates and 
stops. Inverter flashes E.S. after stops. (Refer to instruction for 
F_19 for detail). 
 
 
 
External BASE 
BLOCK 
 
When the external BASE BLOCK signal is activated through the 
multifunction terminal, the inverter stop output immediately and 
flash b.b. for indication. (Refer to instruction for F_19 for detail) 
 
 
Keypad Operation Error Instruction 
INDICATION CONTENT  POSSIBLE CAUSE  COUNTERMEASURE 
 
Motor direction 
locked 
1. Attempt to reverse direction 
when F_22 = 1 
 
2.  Attempt to set F_22 to 1 when 
F_04 = 1 
1. Adjust F_22 to 0 
 
 
2. Adjust F_04 to 0 
 
 
 
Keypad 
operation error 
 
1. Press  ▲ or  ▼  keys when 
F_11=1 or under sp1 operation 
 
2. Attempt to modify F_29 
 
3.Attempt to modify parameter that 
is not allowed to be modified 
during operation (refer to 
parameter list) 
1. Use  ▲ or ▼ keys to 
adjust frequency setting 
only after F_11=0 
 
2. Do not modify F_29 
 
3. Modify in stop mode 
 
 
Parameter 
setting error 
 
1. F_6≦F_7 
 
1. F_6 > F_7 
 
 
SP0 
LOC 
Er1 
Er2 
E.S. 
b.b. 
SP2 
SP1