Malfunction Indications and Countermeasures 
1.  Manual reset inoperative malfunctions 
INDICATION CONTENT  POSSIBLE CAUSE  COUNTERMEASURE 
 
 
Program error 
 
Outside noise interference
Place a RC surge absorber in 
parallel with the noise 
generating magnetic contact 
 
 
EEPROM error 
 
 
EEPROM defective 
 
Replace EEPROM 
 
Voltage too 
high while not 
operating 
1. Power source voltage too 
high. 
2.Detection circuitry       
defective 
1. Examine the power supply 
 
2. Return the inverter for repair 
 
Voltage too low 
while not 
operating 
1. Power source voltage too 
low. 
2. Detection  circuitry 
defective. 
1. Examining the power supply 
 
2. Return the inverter for repair 
 
Inverter over 
heat while not 
operating 
1. Detection circuit defective.
 
2. Environment  over-heat  or 
poor ventilation 
1. Return the inverter for repair 
 
2. Improve ventilation 
 
 
2. Manual reset operative malfunctions (Auto-Reset inoperative) 
INDICATION CONTENT  POSSIBLE CAUSE  COUNTERMEASURE 
 
Over-current at 
stop condition 
 
Detection circuit malfunction 
 
Return the inverter for repair 
 
 
Motor over-load 
 
1. Loading too large 
 
2. Improper V/F model setting
 
3. Improper F_18 setting 
 
1. Increase capacity of motor 
 
2. 
djust to use a proper V/F curve 
setting 
 
3. Adjust F_18 according to 
instruction 
 
Inverter over-load 
 
1. Loading too large 
 
2. Improper V/F model setting
1. Increase capacity of inverter 
 
2. 
djust to use a proper V/F curve 
setting 
 
CPF 
EPR 
OV 
LV 
OH 
OC 
OL1 
OL2