E2-202/203/401/402/403—N4X(IP65)TYPE INSTALLATION: 
T1  T2  T3
3 Phases
IM
220-240V
380-480V
Single/ThreePhases
DATA
FUN
DSP
ENT
RUN
RESET
STOP
REV-0-FWD
SWITCH
Potentiometer
POWER
SWITCH
L1(L) L2(N) L3 
210.0mm
274.5mm
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2.Power supply cable :         4. Torque value of  Screw : 
  E2-200 #12AWG(3.5mm²)       (1).Power/Motor cable(TM1, 
  E2-400 #16AWG(1.25mm²)          TM3)  
3. Motor cable :                              Terminal : 8 kgf-cm(6.94 in-lb) 
  E2-200 #14AWG(2.0mm²)       (2).Remote control wire : 
  E2-400 #16AWG(1.25mm²)          4 kgf-cm(3.47 in-lb)  
                                                  (3).Outer Cover (M4) :  
8kgf-cm(6.94 in-lb) 
 
 
 
 
 
NOTE: 
1.POWER SWITCH,REV-0-FWD SWITCH 
AND Potentiometer are only for 
E2-202~403-N4S TYPE 
 
CIRCUIT DIAGRAM 
 
NOTE: 
(1).Input source:single-phase(L1(L),L2(N),
) ensuring  
that it is connected to a 200/240 supply or three-plase 
(L1 (L), L2 (N), L3, 
)ensuring that it is connected 
to a 200/240,380/480V supply.   
(2).Output Motor: three-phase (
, T1, T2, T3). 
Caution: 
.Do not start or stop the inverter using the main 
circuit power. 
.FOR E2-202~403--N4S TYPE: 
 Please always remain REV-0-FWD switch at 0 
position. In order to keep inverter has no 
running signal before power-on again after 
power supply interrupted.Otherwise, injury may 
result.  
.FOR E2-202~403--N4 TYPE: 
 Please always remain RE or FW switch at OFF 
position. In order to keep inverter has no 
running signal before power-on again after 
power supply interrupted.Otherwise, injury may 
result.