11
 
 
 
 Suitable optional and Wiring Specification 
Molded-Case Circuit Breaker / Magnetic Contact 
z  Warrantee does not apply to damage caused by the following situations: 
 
(1)  Damage to the inverter caused by the lack of appropriate molded-case circuit breaker or 
when a circuit breaker with too large of capacity is installed between the power supply and 
the inverter. 
 
(2)  Damage to the inverter caused by the magnetic contact, phase advancing capacitor, or 
surge-protector installed between the inverter and the motor. 
 
Model Type   1P2/1P5/2P2/2P5  101/201/202 203  401/402/403
Molded-case circuit breaker   15A  20A  30A  15A 
Primary Circuit Terminal (TM1) 
 
 
Wire dimension 
(#14AWG) 2.0mm
2
 
Terminal screw M3 
Wire dimension 
(#14AWG) 
2.0m m
2
 
Terminal screw 
M3/M4 
Wire dimension 
3.5mm
2
 
Terminal screw 
M4 
Wire dimension 
3.5mm
2
 
Terminal screw 
M4 
Signal Terminal (TM2) 
1~11 
Wire dimension 0.75mm
2  
(#18 AWG), Terminal screw M3 
 Use copper conductors only size field wiring based on 80 degrees C wire only. 
 
z  Please utilize three-phase squirrel-cage induction motor with appropriate capacity. 
 
z  If the inverter is used to drive more than one motor, the total capacity must be smaller 
than the capacity of the inverter. Additional thermal overload relays must be installed in 
front of each motor. Use the Fn_18 at 1.0 times of the rated value specified on the motor 
nameplate at 50Hz, 1.1 times of the rated value specified on the motor nameplate at 60Hz. 
 
z  Do not install phase advancing capacitors, LC, or RC component between the inverter and 
the motor. 
 
 
 
 
 
 
 
 
 