Note: The behaviour contrasts with a door on a V8 Four-Door Controller, which
only reports unsecured when the door’s relay is active.
Allow OUT reader access when TZ invalid
If selected, OUT readers will allow access even if a user’s door group has an
invalid time zone.
Programming shunt, egress and passback options
Options for shunting, egress and anti-passback for a door are configured on the
Shunt/Egress/Passback tab of the Doors/Lifts form.
The following figure shows the Shunt/Egress/Passback tab of the Doors/Lifts
form:
Shunt options
Shunting is a procedure that stops an open door causing an alarm for a set time.
Shunt type
This field defines shunt conditions. The options are:
No shunting – The door will not be shunted.
Input shunting – The door will be shunted and will generate a forced door
alarm if it is left open (i.e. Door input 1 is unsealed) longer than the
programmed Shunt time (or Ext. shunt time, if applicable).
Input shunting & DOTL – The door will be shunted and will generate a
DOTL (Door Open Too Long) alarm if it is left open (i.e. Door input 1 is