Setting Display
SET HEAT ROOM
Set the room heating temperature for the event.
Access Level: Installer, User Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Room Sensor On or Sensor 1 or 2 is
set to Room.
Default: 70°F (21.0°C)
SET HEAT ROOM
Set the room heating temperature for the event.
Access Level: Installer, User Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Room Sensor On or Sensor 1 or 2 is
set to Room and Schedule is set to On.
Default: 65°F (18.5°C)
SET COOL ROOM
Set the room cooling temperature for the event.
Access Level: Installer, User Range: 50 to 100°F (10.0 to 38.0°C)
Conditions: Room Sensor On or Sensor 1 or 2 is
set to Room.
Default: 78°F (25.5°C)
SET COOL ROOM
Set the room cooling temperature for the event.
Access Level: Installer, User Range: 50 to 100°F (10.0 to 38.0°C)
Conditions: Room Sensor On or Sensor 1 or 2 is
set to Room and Schedule is set to On.
Default: 85°F (29.5°C)
SET FLOOR
Set the floor heating temperature for the event.
Access Level: Installer, User
Range: OFF, 40 to 122°F
(OFF, 4.5 to 50.0°C)
Conditions: Sensor 1 or 2 is set to Floor. Default: 72°F (22.0°C)
Set Temp Menu
Fan Menu
Setting Display
FAN
Select if the fan should operate continuously (On)
or only together with the heating or cooling equip-
ment (Auto).
Access Level: Installer, User Range: Auto or On
Conditions: Only available when FAN MODE is
not set to OFF and a room temperature sensor is
available.
Default: Auto