EasyManua.ls Logo

Tekmar 521 - Installation; Preparation and Materials; Installation Location; Removing the Thermostat Base

Tekmar 521
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2020 521_D - 12/20
4 of 28
A Watts Water Technologies Company
Preparation
Installation
Choose the placement of the thermostats early in the construction process to enable
proper wiring during rough-in.
Consider the following:
Interior Wall.
Keep dry. Avoid potential leakage onto the control.
Relative Humidity less than 90%. Non-condensing environment.
No exposure to extreme temperatures beyond 32-122°F (0-50°C).
No draft, direct sun, or other cause for inaccurate temperature readings.
Away from equipment, appliances, or other sources of electrical interference.
Easy access for wiring, viewing, and adjusting the display screen.
Approximately 5 feet (1.5 m) off the finished floor.
The maximum length of wire is 500 feet (150 m).
Strip wire to 3/8" (10 mm) for all terminal connections.
Use standard 5 conductor, 18 AWG wire.
Installation Location
------------------------------------------------ ------------------------------------------------
tekmar or jeweller screwdriver
Phillips head screwdriver
Wire Stripper
Tools Required
----------------------------------------------------- -----------------------------------------------------
Materials Required
------------------------------------------------- -------------------------------------------------
18 AWG LVT Solid Wire
(Low Voltage Connections)
Removing The Thermostat Base
To remove the thermostat base:
Locate the tab on the bottom of the thermostat.
Push the tab with either your thumb or with a
screwdriver.
Lift the thermostat front away from the
thermostat’s base.