EasyManua.ls Logo

Telect 009-8005-0404 - Figure 12 - TPA Output Lug Connections; Figure 13 - GMT Output Lug Connections

Telect 009-8005-0404
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© Telect, Inc., All Rights Reserved, 123518-9 A0
1.509.926.6000 :: telect.com
10
Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel
Power :: 009-8005-0404 :: 009-8005-0404G :: 009-8005-0404L
24. Make sure none of the fuse positions contain
operable fuses.
25. For TPA output wiring, crimp single-hole lugs onto
one end of #18 to #6 AWG copper output wires,
as required by NEC. (Work with one output wire
at a time.)
26. Clean the panel terminals and lugs with a
nonabrasive, nonmetallic pad.
2 7. If required, lightly coat anti-oxidant on lugs and
output BATTERY and RETURN terminals, and
then connect lug to terminals, as shown in
Figure 12. (NEC species only one lug and load
at each output terminal.)
28. Tighten the nuts to 20 in.-lb. (~2.3 N•m).
29. Connect the other end of the output wire to load.
30. For GMT output wiring, use #20 to #12 AWG
copper wire. (Work with one wire at a time.) At
the panel end of the wire, either
• Crimp a single-hole ring or fork lug, as required
by NEC, or
• Strip 3/8 in. (1 cm) of insulation for a bare
wire connection.
3 1. Clean the panel terminals and lug (if applicable)
with a nonabrasive, nonmetallic pad.
32. If required, lightly coat anti-oxidant on the lug/wire
and output BATTERY and RETURN terminals.
33. Connect to the terminals, as shown in Figure13.
(NEC species only one load at each output
terminal.)
34. Tighten the panhead screws to no more than
8 in.-lb. (~1 N•m).
35. Connect the other end of the output wire to load.
Figure 12 - TPA Output Lug Connections
Figure 13 - GMT Output Lug Connections