EasyManua.ls Logo

TempMaster OmniElite - Heating Performance Data - Gas;Electric Heat

Default Icon
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TEMPMASTER
38
FORM TPM3-EG1 (518)
Heating Performance Data – Gas/Electric Heat
GAS HEATING
ELECTRIC HEATING
TABLE 10 - GAS HEAT PERFORMANCE DATA
UNIT
GAS INPUT CAPACITY
(BTU/HR X 1000)
MAXIMUM OUTPUT
CAPACITY
(BTU/HR X 1000)
AIRFLOW
MINIMUM
TEMP. RISE
(°F)
120–150 1125 900 19350 43
NOTE:
Gas valve rated for 0.5 psig. If gas pressure greater than 0.5 psig, then a gas pressure regulator is required.
Minimum gas pressure is 4.5 iwg.
TABLE 11 - ELECTRIC HEAT PERFORMANCE DATA
UNIT SIZE (KW)
HEAT CAPACITY
(MBH)
AIRFLOW MIN
(CFM)
MAX TEMP RISE
(°F)
120–150
TON
80 273 15,000 22
108 369 15,000 28
150 512 15,000 36
200 683 15,000 47
250 854 15,000 44

Related product manuals