Heating Performance Data – Gas/Electric Heat
GAS HEATING
ELECTRIC HEATING
TABLE 10 - GAS HEAT PERFORMANCE DATA
UNIT
GAS INPUT CAPACITY
(BTU/HR X 1000)
MAXIMUM OUTPUT
CAPACITY
(BTU/HR X 1000)
AIRFLOW
MINIMUM
TEMP. RISE
(°F)
120–150 1125 900 19350 43
NOTE:
Gas valve rated for 0.5 psig. If gas pressure greater than 0.5 psig, then a gas pressure regulator is required.
Minimum gas pressure is 4.5 iwg.
TABLE 11 - ELECTRIC HEAT PERFORMANCE DATA
UNIT SIZE (KW)
HEAT CAPACITY
(MBH)
AIRFLOW MIN
(CFM)
MAX TEMP RISE
(°F)
120–150
TON
80 273 15,000 22
108 369 15,000 28
150 512 15,000 36
200 683 15,000 47
250 854 15,000 44