Operating Instructions
42
If all compartments are to be maintained at the
same temperature and all evaporators are required
to operate, it is recommended that the dividing
bulkhead doors be closed to allow correct
temperature management in each compartment.
Figure 16: Same Temperatures in each
Compartment, Host and Remote Running,
Bulkhead Closed
Post Load Procedure
1. Make sure all the doors are closed and locked.
2. Start the unit if it was shut off to load (see
“Restarting Unit”).
3. Make sure the setpoints are at the desired
settings.
4. One-half hour after loading, manually initiate
defrost cycles in each compartment. If the
evaporator coil sensor temperature is below
45 F (7 C), the evaporator will defrost. The
microprocessor will terminate defrost
automatically when the evaporator coil
temperature reaches 58 F (14 C) or the
evaporator has been in the Defrost mode for
30 or 45 minutes (depending on setting).
Post Trip Checks
1. Wash the unit.
2. Check for leaks.
3. Check for loose or missing hardware.
4. Check for physical damage to the unit.