Phase overcurrent 50/51 - Standard inverse time curve (IEC 60255-3/BS142 type A)
F_51-IECA-Char.ai
1.1
2 3 4 5 6 7 8 9 10 20
I
/I>inv
0.01
0.1
1
10
100
1000
10000
t [s]
t>
inv
= 10 s
t>
inv
= 60 s
t>
inv
= 5 s
t>
inv
= 1 s
t>
inv
= 0.5 s
t>
inv
= 0.2 s
t>
inv
= 0.1 s
t>
inv
= 0.02 s
t =
t>
inv
·
[(I/I>
inv
)
0.02
-1]
0.14
Note: match of operating and setting time takes place when I/I>
inv
= 700