EasyManua.ls Logo

Thytronic NA30

Thytronic NA30
237 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDIX
162
NA30 - Manual - 04 - 2022
Phase overcurrent 50/51 - Standard inverse time curve (IEC 60255-3/BS142 type A)
F_51-IECA-Char.ai
1.1
2 3 4 5 6 7 8 9 10 20
I
/I>inv
0.01
0.1
1
10
100
1000
10000
t [s]
t>
inv
= 10 s
t>
inv
= 60 s
t>
inv
= 5 s
t>
inv
= 1 s
t>
inv
= 0.5 s
t>
inv
= 0.2 s
t>
inv
= 0.1 s
t>
inv
= 0.02 s
t =
t>
inv
·
[(I/I>
inv
)
0.02
-1]
0.14
Note: match of operating and setting time takes place when I/I>
inv
= 700

Table of Contents

Related product manuals