Earth Ground Installation
 
IMPORTANT! The satellite surge protection components cannot properly function unless an efficient pathway to earth 
ground is provided. The ground path must be as direct as possible, without sharp bends and must not exceed 30 ohms 
resistance (when measured with an earth ground resistance test device). A resistance reading of 0–10 ohms is considered 
excellent, 11–20 ohms is acceptable and 21–30 is considered marginal. All electrical components throughout the irrigation 
system should be grounded in a manner which provides the same ground potential.
The following instructions depict one of 
several acceptable earth grounding methods. 
Due to variables in soil composition and 
terrain, the method shown may not be suitable 
for your installation site. Contact your local 
Toro distributor for assistance and availability 
of the required earth ground resistance test 
instrument. Recommended ground testers 
are: AEMC Instruments, model 3710 clamp-on 
tester, or Biddle Megger, model 250260  
(or equivalent).
Procedure
 1. Drive a 5/8” by 8’ (17 mm x 2.4 m) 
copper-clad steel rod into well moistened 
soil not less than 8’ (2.5 m) or more than 
12’ (3.7 m) from the satellite. The top of 
the ground rod should be 12” (30.5 cm) 
below grade level. See Figure 4.
 2. Using a 5/8” (17 mm) clamp or “Cad weld” 
fastener, attach a 6 AWG (10 mm
2
) solid 
copper wire near the top of the ground 
rod. Avoiding wire bends of less than 
8” (20.3 cm) radius and more than 90°, 
route the wire through conduit into the controller cabinet. Secure the wire to the large copper ground lug. See Figure 4. 
 Note: Make sure the soil surrounding the ground rod(s) remains well moistened at all times. The addition of some form of 
irrigation may be required if the satellite is installed in a non-irrigated location. 
 3. Measure the ground resistance per the instructions provided with the ground test instrument. A reading of 0 ohms is 
optimum, up to 10 ohms is good and 11-30 ohms is acceptable in most cases. If the resistance exceeds the acceptable 
limit, additional ground rod(s) can be installed at a distance equal to twice the buried depth of the first rod; i.e., 16’ 
(4.9 m). Interconnect the ground rods using 6 AWG (10 mm
2
) solid copper wire and test again. If the measured ground 
resistance continues to read above the acceptable limit, contact your local Toro distributor for further assistance and 
recommendations.
 Note: Installing a round valve box over the ground rod enables the ground rod to be easily located as well as providing 
access to the ground wire connection(s).
Figure 4
Chassis Ground Lug
Valve Box
6 AWG (10mm
2
) 
Ground Wire
12” 
(30.5cm)
8” (20.3cm) 
Radius Minimum
Ground Wire To 
Additional Rod(s) 
(Optional)
Copper-Clad 
Ground Rod
8’–12’ (2.4m–3.7m)
90
o