Field Wire Installation
 
CAUTION: The Network VP satellite is 
capable of operating up to 32 stations 
and the pump/master valve circuit 
concurrently. To prevent possible 
controller damage, total current load for all 
field outputs operating concurrently must 
not to exceed 3.2A. If more than one valve 
per station is required, calculate the total 
in-rush current load which would be 
imposed in the maximum operating 
conditions and use this value as a guide 
during installation and operation of the 
controller.
Procedure
1. Attach the control and common wires to 
each valve and/or valve-in-head solenoid 
leads using an approved waterproof splicing 
method. Route the wires into the controller 
cabinet through the 3” (76mm) conduit.
2. If automatic pump start is required, refer to 
the applicable wiring diagram in Figure 7 and install 
accordingly.
 
CAUTION: Do not connect the pump starter 
directly to the controller’s pump start circuit. 
Damage to the controller will result. 
Note: The pump circuit can also be utilized to control a 
master valve if required.
3. Secure the field common wire(s) and pump start relay 
(or master valve) wire to the appropriate terminals 
on the Pump/Com module OR (optional) Pump/Com 
Surge Protection module. See Figure 8.
4. Momentarily touch each valve control wire to the 
Hot Post to activate and identify the corresponding 
valve(s).
5. Secure the valve control wires to the station terminals 
in the preferred order of operating sequence. Station 
terminals are numbered left to right, 1–32 (front) and 
33–64 (back). See Figure 9.
Note: A 3-position switch is provided on the Pump/Com 
module for additional control of the pump relay circuit. 
In addition, the optional station terminal modules 
with optional control switches have one switch for 
each station output. See Figures 8 and 9. The three switch 
positions control the circuits as follows:
On – Manually activates the circuit. The pump or station will 
remain on until the switch is moved to the Auto or Off position.
Off – Switches the circuit off, preventing pump or station 
operation from the satellite.
Auto – The circuit is automatically activated by the controller 
during automatic or manual watering operation.
As an added lightning protection measure, the field common 
circuit is normally open when the controller is inactive. 
Therefore, to use the field output control switches for manual 
operation, the common circuit must be engaged first.  
Press the Field Common Engage push button switch to 
activate the circuit. The Field Common Indicator Lamp will 
turn on when the circuit is active. The common circuit will 
automatically disconnect upon completion of an automatic or 
manually activated watering operation initiated through the 
timing mechanism. The circuit can also be disconnected by 
momentarily switching the power supply off. 
 
CAUTION: To prevent damage to the 3.2A field output circuit fuse,  
do not exceed 3.2A load when manually activating multiple field outputs. 
1
PUMPCOMMON
PUMPCOMMON
ON
AUTO
OFF
Figure 8
Pump/Com Module
Optional Pump/Com & 
Communication Surge 
Protection Module
 Field Common  
 Terminals
 Field Common  
 Terminals 
 Pump  
 Terminal
 Pump  
 Terminal
Pump Circuit 
Switch
Field Common 
Engage Switch
Multiple Controllers
Single Controller
Pressure Switch With 
Controller Override
Starter 
Power 
Source
Starter 
Power 
Source
Starter 
Power 
Source
Pump Power 
Source
Pressure Switch
Pump Power 
Source
Pump Power 
Source
Relay  
24 VAC 
.75A Max.
Relay  
24 VAC 
.75A Max. 
(Typical)
Relay  
24 VAC 
.75A Max.
Pump
Pump
Pump
Pump
Pump
Pump
Pump
Com
Com
Com
Com
Magnetic 
Pump 
Starter
Magnetic 
Pump 
Starter
Mag. 
Pump 
Starter
To Other 
Controllers
Figure 7
Station Output Control 
Switches (Optional) 
Hot Post
Standard 
Terminal Block
Surge Protection Terminal 
Block (Optional) 
Figure 9
3-Amp Fuse
1-Amp Fuse
Station Output Terminals
Station Output Terminals