168 ACE-tronics G9 ASD Installation and Operation Manual
Plugging
Program Crane/Hoist
This parameter Enables/Disables the Plugging feature of the ASD. Plugging
assigns alternate Acceleration and Deceleration time settings to be used during
a direction change only.
The Plugging acceleration and deceleration times are set at parameters F514
and F515, respectively.
This parameter is further defined by the ACC/DEC Pattern selection of F516.
Settings:
Disabled
Enabled
Direct Access Number F494
Parameter Type — Selection
Factory Default Disabled
Changeable During RunYes
PM Motor Constant 1 (D Axis Inductance)
Program Motor PM Motor
This parameter is used with synchronous motor applications only.
Contact ACE World Companies Customer Support Center for information on
this parameter.
Direct Access Number F498
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunYes
Minimum — 0
Maximum — 100
Units — %
PM Motor Constant 2 (Q Axis Inductance)
Program Motor PM Motor
This parameter is used with synchronous motor applications only.
Contact ACE World Companies Customer Support Center for information on
this parameter.
Direct Access Number F499
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunYes
Minimum — 0
Maximum — 100
Units — %
Acceleration Time 2
Program Special Acc/Dec 1 – 4
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency for the #2 Deceleration profile.
The Accel/Decel pattern may be set using F503. This parameter may be further
defined by the settings of F506F509.
Note: An acceleration time shorter than that which the load will allow
may cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel, Stall, and Ridethrough settings may
lengthen the actual acceleration times.
Direct Access Number F500
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunYes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds