ACE-tronics G9 ASD Installation and Operation Manual 169
Deceleration Time 2
Program Fundamental Acc/Dec 1
This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz for the #2 Deceleration profile.
The Accel/Decel pattern may be set using F503. This parameter may be further
defined by the settings of F506 – F509.
Note: A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
actual deceleration times.
Direct Access Number — F501
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
F501 F501