Parts specification
Multi Controller unit
Specification of 3-pipe Multi Controller parts
Model name RBM-Y1034F-PE RBM-Y1044F-PE
Pulse modulating valve EV23RC7, coil DC 12 V
Temperature sensor At 0°C = 32.8 k, 25°C = 10 k, 50°C = 3.6 k
Float switch FS-085-0031
PC board assembly PCB MCC-1222
Power supply transformer Model name FT69
Specification Primary side: AC 240 V, secondary side: AC 12 V
Relay (PC board) G2R-117P, coil DC 12 V
Heater 10.4 W/m
50 W 65 W
Thermal fuse for heater Cut out at 119°C
Heater fuse T1A
Discharge gas side 2-way valve RP100-03, coil AC 240 V
Suction gas side 2-way valve REV-1506DXFQ6, coil AC 240 V
2-way valve NEV202DXF-AC 240 V
2-way valve NEV603DXF-AC 240 V
Note:
Specifications are subject to change without notice.