104
<Service support function list>
SW01 SW02 SW03 7-segment display [A] Function contents
2
1
1
[J . C]
Refrigerant circuit and control communication line check function (Cooling
operation)
2[J . H]
Refrigerant circuit and control communication line check function (Heating
operation)
3 [P . ] Indoor PMV forced full open function
4 [A . 1] Indoor remote control discriminating function
5 [C . ] Cooling test operation function
6 [H . ] Heating test operation function
7 [C . H] Indoor collective start/stop (ON/OFF) function
11 [r
.
d] Outdoor refrigerant recovery operation function (Pump down function)
16 [E
.
r] Error clear function
2
1~16
3 [H . r] Solenoid valve forced open/close function
24~7[F
.
d] Fan forced operation function
215[t
.
o] Outside temperature sensor manual adjustment function
16 1~16
1 [0 1]~[1 6] Indoor No. 1 to 16 unit Indoor individual start/stop (ON/OFF) function
2 [1 7]~[3 2] Indoor No. 17 to 32 unit
3 [3 3]~[4 8] Indoor No. 33 to 48 unit
SW01 SW02 SW03 7-segment display [A/B] Function contents
1 1 1 [U 1] [ E28 ] Follower unit error / Corresponding unit fan operation function