8-7-3. Error clearing function
(1)Clearing from the wired remote control
Error clearing in outdoor unit
Error of the outdoor unit currently detected is cleared by the unit of one refrigerant circuit system to which the indoor
units operated by the remote control is connected. (Error of the indoor unit is not cleared.)
For clearing errors, the service monitor function of the remote control is used.
<Method>
1 Change the mode to service monitor mode by pushing + buttons simultaneously for 4
seconds or more.
2 Using buttons, set CODE No. to “FF”.
3 The display in Section A in the following figure is counted with interval of 5 seconds as
“0005” --> “0004” --> “0003” --> “0002” --> “0001” --> “0000”.
When the count arrives “0000”, the error is cleared.
*However, counting from “0005” is repeated on the display.
4 When button is pushed, the status returns to the normal status.
Error clearing in indoor unit
Error in the indoor unit is cleared by button on the remote control.
(Only error of the indoor unit connected with operating remote control is cleared.)
Section A