Errors Detected by TCC-LINK Central Control Device
Check code
Location
of
detection
Description System status Error detection condition(s) Check items (locations)
Wired
remote
control
Outdoor 7-segment display
Sub-code
C05
TCC-LINK TCC-LINK
central control
device
transmission
error
Continued
operation
Central control device is unable to
transmit signal.
Check for defect in central control
device.
Check for defect in central control
communication line.
Check termination resistance
setting.
C06
TCC-LINK
central control
device reception
error
Continued
operation
Central control device is unable to
receive signal.
Check for defect in central control
device.
Check for defect in central control
communication line.
Check termination resistance
setting.
Check power supply for devices
at other end of central control
communication line.
Check defect in P.C. boards of
devices at other end of central
control communication line.
C12
General-
purpose
device
I/F
Blanket alarm
for general-
purpose device
control interface
Continued
operation
Error signal is input to control
interface for general-purpose
devices.
Check error input.
P30
Differs according to
nature of alarm-causing
error
TCC-LINK Group control
follower unit
error
Continued
operation
Error occurs in follower unit under
group control.
([P30] is displayed on central
control remote control.)
Check check code of unit that has
generated alarm.
(L20 displayed.)
Duplicated
central control
address
Continued
operation
There is duplication in central
control addresses.
Check address settings.