7-2. Applied control of outdoor unit
Optional control P.C. boards provide access to a range of functions as listed below.
Layout of Outdoor Unit Interface P.C. Board
* DIP switch settings and jumper wire statuses vary from function to function.
No. Function
Outdoor unit
for control
P.C. board
connection
Control P.C. board to be used Outdoor unit interface P.C. board setting*
PCDM4UL PCMO4UL PCIN4UL Connector No. DIP SW No. Bit
Jumper to be
removed
1
Power peak-cut Control (Standard) Header unit CN513(blue) SW07 1
Power peak-cut Control (For one
input function)
Header unit CN513(blue) SW07 1 J16
2
Power peak-cut Control (Enhanced
Functions)
Header unit CN513(blue) SW07 1.2
3 Snowfall Fan Control Header unit CN509(black)
4 External master ON / OFF Control Header unit CN512(blue)
5
Night operation (sound reduction)
Control
Header unit CN508(red)
6
Operation Mode Selection Control Header unit CN510(white)
Operation Mode Selection Control
(forced choice)
Header unit CN510(white) J01
7 Error / Operation output Header unit CN511(green)
8 Compressor Operation Output
Individual
outdoor unit
–– CN514(green)
9 Operating Rate Output Header unit CN514(green) SW16 1
Connector layout
Jumper wire layout
DIP switch layout
Interface P.C. Board