EasyManua.ls Logo

Toshiba MMY-MAP0724HT6UL - Troubleshooting Method

Toshiba MMY-MAP0724HT6UL
241 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
108
9-2. Troubleshooting method
The remote controls (main remote control and central control remote control) and the interface P.C. board of an
outdoor unit are provided with an LCD display (remote control) or a 7-segment display (outdoor interface P.C.
board) to display operational status. Using this self-diagnosis feature, the fault site/faulty part may be identified in
the event of a fault by following the method described below.
The list below summarizes check codes detected by various devices. Analyze the check code according to where it is displayed and work out
the nature of the fault in consultation with the list.
When investigating a fault on the basis of a display provided on the indoor remote control or TCC-LINK central control remote control - See
the “TCC-LINK remote control or main remote control display” section of the list.
When investigating a fault on the basis of a display provided on an outdoor unit - See the “Outdoor 7-segment display” section of the list.
When investigating a fault on the basis of a wireless remote control-controlled indoor unit - See the “Light sensor indicator light block” section
of the list.
List of Check Codes (Indoor Unit)
(Error detected by indoor unit)
Check code
Display of receiving unit
Typical fault site Description of error
TCC-LINK central
control or main
remote control
display
Outdoor 7-segment display Indicator light block
Sub-code
Flash
E03
Indoor-remote control periodic
communication error
Communication from remote control or network
adaptor has been lost (so has central control
communication).
E04
Indoor-outdoor periodic
communication error
Signals are not being received from outdoor unit.
E08 E08
Duplicated indoor address
Duplicated indoor address Indoor unit detects address identical to its own.
E10
Indoor inter-MCU communication
error
MCU communication between main controller and
motor microcontroller is faulty.
E18
Error in periodic communication
between indoor header and follower
unit
Periodic communication between indoor header
and follower units cannot be maintained.
F01 ALT
Indoor heat exchanger temperature
sensor (TCJ) error
Heat exchanger temperature sensor (TCJ) has
been open/short-circuited.
F02 ALT
Indoor heat exchanger temperature
sensor (TC2) error
Heat exchanger temperature sensor (TC2) has
been open/short-circuited.
F03 ALT
Indoor heat exchanger temperature
sensor (TC1) error
Heat exchanger temperature sensor (TC1) has
been open/short-circuited.
F10 ALT
Ambient temperature sensor (TA)
error
Ambient temperature sensor (TA) has been open/
short-circuited.
F11 ALT
Discharge temperature sensor (TF)
error
Discharge temperature sensor (TF) has been
open/short-circuited.
F29 SIM P.C. board or other indoor error
Indoor EEPROM is abnormal (some other error
may be detected).
L03 SIM Duplicated indoor group header unit There is more than one header unit in group.
L07 SIM
Connection of group control cable
to stand-alone indoor unit
There is at least one stand-alone indoor unit to
which group control cable is connected.
L08 L08 SIM Indoor group address not set
Address setting has not been performed for one or
more indoor units (also detected at outdoor unit
end).
L09 SIM Indoor capacity not set
Capacity setting has not been performed for indoor
unit.
L20 SIM Duplicated central control address
There is duplication in central control address
setting.
L30 L30
Detected indoor unit No.
SIM
Indoor external error input
(interlock)
Unit shutdown has been caused by external error
input (CN80).
P01 ALT Indoor AC fan error
Indoor AC fan error is detected (activation of fan
motor thermal relay).
P10 P10
Detected indoor unit No.
ALT Indoor overflow error Float switch has been activated.
P12 ALT Indoor DC fan error
Indoor DC fan error (e.g. overcurrent or lock-up) is
detected.
P31 ALT Other indoor unit error
Follower unit cannot be operated due to header
unit alarm (E03/L03/L07/L08).
IPDU: Intelligent Power Drive Unit (Inverter P.C. board)
: Lighting, : Flashing, : Goes off
ALT.: Flashing is alternately when there are two flashing LED
SIM: Simultaneous flashing when there are two flashing LED
Operation Timer Ready

Table of Contents

Related product manuals