Toshiba MMY-MAP0724HT6UL - Power Peak-Cut Control (Extended)

Toshiba MMY-MAP0724HT6UL
241 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52
<SW07 Bit 2 OFF (two-step control)>
Power peak-cut control is enabled as long as SW1, as shown on the wiring diagram, is ON (continuously).
Note 1: Specifications of display relay contact
The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
The optional P.C. board should be connected to the header outdoor unit (U1).
7-2-2. Power peak-cut control (extended)
Operation
An external power peak-cut control signal limits the peak capacity of the outdoor unit.
L1: Power peak-cut control indication lamp
SW1: Power peak-cut control ON switch*1
SW2: Power peak-cut control OFF switch*1
*1 The inputs of SW1 and SW2 can be either pulse (100 msec or wider) or step signals.
* Be sure to provide a contact for each terminal.
Extended power peak-cut control settings
Specifications of display relay contact
Note 1: Specifications of display relay contact
The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
The optional P.C. board should be connected to the header outdoor unit (U1).
Jumper wire
J16
Input
SW1
SW07 Bit 1 Indicator relay
Bit 1 OFF Bit 1 ON (L1)
Cut
ON 0% (forced stop) 60% capacity (upper limit regulated) OFF
OFF 100% (normal operation) 100% (normal operation) ON
<Electrical Rating>
24 V or less (AC / DC), 10 mA or more, 1 A or less (non-conductive load)
Indication lamp
External power peak-cut control
signals
Peak capacity
I/F SW07 Bit 1
L1 SW1 SW2 OFF ON
OFF OFF OFF 100% (normal operation) 100% (normal operation)
ON ON OFF 80% (upper limit regulated) 85% (upper limit regulated)
ON OFF ON 60% (upper limit regulated) 75% (upper limit regulated)
ON ON ON 0% (forced stop) 60% (upper limit regulated)
<Electrical Rating>
24 V or less (AC / DC), 10 mA or more, 1 A or less (non-conductive load)
Header outdoor unit
L1: Display lamp suring power peak cut control
Locally procured
Outdoor unit
interface PCB
Connection cable
Shield wire
Shield wire
Display
relay
Optional PCB
[OPERATION]
Power
supply
For SW1 and SW2, be sure to provide
no-voltage contacts for each terminal.