Check code
Location
of
detection
Description System status Error detection condition(s) Check items (locations)
Wired
remote
control
Outdoor 7-segment display
Check
code
Sub-code
P22 P22
0: IGBT circuit
1: Position
detection circuit
error
3: Motor lockup
error
4: Motor
current
detection
C: TH sensor
temperature
error
D: TH sensor
error
E: Inverter DC
voltage error
(outdoor fan)
Note:
Although
letters 0 to F
appear at
locations
indicated by
”, please
ignore them.
IPDU Outdoor fan
IPDU error
All stop (Sub code: 0)
Fan IPDU over current protection
circuit
Flow of current equal to or greater
than the specified value is detected
during startup of the fan.
Check fan motor.
Check for defect in fan IPDU P.C.
board.
All stop (Sub code: 1)
Fan IPDU position detection circuit
Position detection is not going on
normally.
Check fan motor.
Check connection of fan motor
connector.
Check for defect in fan IPDU P.C.
board.
All stop (Sub code: 3)
Gusty wind, an obstruction, or
another external factor
Speed estimation is not going on
normally.
Check fan motor.
Check for defect in fan IPDU P.C.
board.
All stop (Sub code: 4)
Fan IPDU over current protection
circuit
Flow of current equal to or greater
than the specified value is detected
during operation of the fan.
Check fan motor.
Check connection of fan motor
connector.
Check for defect in fan IPDU P.C.
board.
All stop (Sub code: C)
Higher temperature than the
specified value is detected during
operation of the fan.
Check fan motor.
Check for defect in fan IPDU P.C.
board.
All stop (Sub code: D)
The resistance value of the sensor
is infinite or zero (open or short
circuit).
Check for defect in fan IPDU P.C.
board.
All stop (Sub code: E)
Fan IPDU DC voltage protection
circuit
The DC voltage higher or lower than
the specified value is detected.
Check power voltage of the main
power supply.
Check for defect in fan IPDU P.C.
board.
Check connection of fan IPDU
P.C. board.
P26 P26
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
IPDU G-TR short-
circuit
protection error
All stop Overcurrent is momentarily
detected during startup of
compressor.
Check connector connection and
wiring on A3-IPDU P.C. board.
Check for defect in compressor
(layer short-circuit).
Check for defect in outdoor P.C.
board (A3-IPDU).
P29 P29
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
IPDU Compressor
position
detection circuit
error
All stop Position detection is not going on
normally.
Check wiring and connector
connection.
Check for compressor layer
short-circuit.
Check for defect in A3-IPDU P.C.
board.
P31
Indoor
unit
Other indoor
error
(group follower
unit error)
Stop of
corresponding
unit
There is error in other indoor unit in
group, resulting in detection of E07/
L07/L03/L08.
Check indoor P.C. board.