123
Check code
Location
of
detection
Description System status Error detection condition(s) Check items (locations)
Wired
remote
control
Outdoor 7-segment display
Check
code
Sub-code
H06 H06
I/F Activation of
low-pressure
protection
All stop Low-pressure Ps sensor detects
operating pressure lower than
0.02MPa.
Check service valves to confirm
full opening
(both gas and liquid sides).
Check outdoor PMVs for clogging
(PMV1, 2).
Check for defect in SV2 or SV4
circuits.
Check for defect in low-pressure
Ps sensor.
Check indoor filter for clogging.
Check valve opening status of
indoor PMV.
Check refrigerant piping for
clogging.
Check operation of outdoor fan
(during heating).
Check for insufficiency in
refrigerant quantity.
H07 H07
0
: I/F Low oil level
protection
All stop Operating compressor detects
continuous state of low oil level for
about 2 hours.
<All outdoor units in corresponding
line to be checked>
Check balance pipe service valve
to confirm full opening.
Check connection and installation
of TK1, TK2, TK3, TK4, and TK5
sensors.
Check resistance characteristics
of TK1, TK2, TK3, TK4, and TK5
sensors.
Check for gas or oil leak in same
line.
Check for refrigerant entrapment
inside compressor casing.
Check SV3A, SV3B, SV3C,
SV3D, SV3E, and SV3F valves
for defect.
Check oil return circuit of oil
separator for clogging.
Check oil equalizing circuit for
clogging.
H08 H08
01: TK1 sensor
error
02: TK2 sensor
error
03: TK3 sensor
error
04: TK4 sensor
error
05: TK5 sensor
error
I/F Error in
temperature
sensor for oil
level detection
All stop Sensor resistance is infinity or zero
(open/short circuit).
Check connection of TK1 sensor
connector.
Check resistance characteristics
of TK1 sensor.
Check for defect in outdoor P.C.
board (I/F).
All stop Sensor resistance is infinity or zero
(open/short circuit).
Check connection of TK2 sensor
connector.
Check resistance characteristics
of TK2 sensor.
Check for defect in outdoor P.C.
board (I/F).
All stop Sensor resistance is infinity or zero
(open/short circuit).
Check connection of TK3 sensor
connector.
Check resistance characteristics
of TK3 sensor.
Check for defect in outdoor P.C.
board (I/F).
All stop Sensor resistance is infinity or zero
(open/short circuit).
Check connection of TK4 sensor
connector.
Check resistance characteristics
of TK4 sensor.
Check for defect in outdoor P.C.
board (I/F).
All stop Sensor resistance is infinity or zero
(open/short circuit).
Check connection of TK5 sensor
connector.
Check resistance characteristics
of TK5 sensor.
Check for defect in outdoor P.C.
board (I/F).
H15 H15
I/F TD2 sensor
miswiring
(incomplete
insertion)
All stop Air discharge temperature of (TD2)
does not increase despite
compressor 2 being in operation.
Check installation of TD2 sensor.
Check connection of TD2 sensor
connector and wiring.
Check resistance characteristics
of TD2 sensor.
Check for defect in outdoor P.C.
board (I/F).