162
Check code Check code name Cause
Compressor position detective
circuit error
1. Wire/connector connection error
2. Compressor error
3. A3-IPDU P.C. board error
Sub-code:
01: Compressor 1, 02: Compressor 2, 03: Compressor 3
Are connector
connection and wiring
normal?
Is the unit grounded?
Is not winding
shorted? (Is winding
resistance 0.1 to
0.4Ω?)
Is not winding
opened?
Check A3-IPDU P.C. board.
Failure Replace
Check and correct circuit and
cables such as wiring to
compressor, etc.
Compressor error Replace
Compressor error Replace
Compressor error Replace
Other indoor error
(Group follower unit error)
Another indoor unit in the group is abnormal.
When the header unit of the group detected error [E03], [L03], [L07] or [L08], the follower unit of the group displays