(1)Display of System Information (Displayed on Header Outdoor Unit Only)
SW01 SW02 SW03 Display detail
1
1
3
Unused AB
2
System capacity A […6]~[10]:6 to 20 ton
B [ton]
3
No. of outdoor units A […1]~[…2]:1 to 2
B […P]
4
No. of indoor units connected /
No. of units with cooling thermo ON
A […0.]~[48.]:0 to 48 (No. of units connected)
B [C…0]~[C48]:0 to 48 (No. of units with cooling thermo ON)
5
No. of indoor units connected /
No. of units with heating thermo ON
A […0.]~[48.]:0 to 48 (No. of units connected)
B [H…0]~[H48]:0 to 48 (No. of units with heating thermo ON)
6
Amount of compressor command
correction
A Value displayed in hexadecimal format
B
7
Release control A Normal: [r. …], During release control: [r.1]
B–
8
Oil equalization control Normal: [oiL-0]
During oil equalization control: [oiL-1]
9
Oil equalization request A Displayed through LED segment lighting pattern
B
10
Refrigerant/oil recovery operation A Oil recovery in cooling: [C1], Normal: [C …]
B Refrigerant recovery in heating: [H1], Normal: [H …]
11
Automatic addressing A [Ad]
B During automatic addressing: [… FF], Normal: [… … …]
12
Power pick-cut A [dU]
B Normal: [… … …], During 50-90% capacity operation: [_50-_90]
While control is based on BUS line input: [E50-E90]
13
Optional control (P.C. board input) Displays optional control status A B
Operation mode selection: During priority heating (normal) h.. ...
Priority cooling c.. ...
Heating only H.. ...
Cooling only C.. ...
Priority given to No. of indoor units in operation n.. ...
Priority given to specific indoor unit U.. ..
.
External master ON/OFF: Normal .…. ...
Start input .1. ...
Stop input .0. ...
Night operation: Normal ..…...
Start input ..1...
Snowfall operation: Normal .. .…..
Start input .. .1..
14
Optional control
(BUS line input)
Same as above
15
Unused
16
–A
B–
Display section A Display section B
Outdoor unit No.
If element F shown on sketch at right turned on:
Header unit oil equalization request
If element C shown on sketch at right turned on:
Follower unit oil equalization request