197
<Installing compressor>
Install a compressor by following the dismantling procedure in reverse.
Notes:
Although a compressor is provided with only two hexagonal bolts, it is standard.
The tightening torque of the hexagonal bolts, used to mount the compressor, is 200kg/cm.
If oil has been drawn from the accumulator, repair the cut pipe through pinching and brazing.
After replacement of the compressor, be sure to replace the compressor lead.
(Repair part code of compressor lead : 43160638)
<Vacuum-pumping>
(Single outdoor unit system)
Before performing vacuum-pumping, fully open PMV1, 2 and 4. If they are closed, the heat exchangers of the
outdoor unit cannot be vacuum-pumped.
Connect a vacuum pump consecutively to the check joints placed in the liquid and discharge pipes and on the
high-pressure side of the suction pipe, and turn it on.
Operate the vacuum drying until the vacuum gauge indicates 1 mmHg.
<Method to fully open PMV manually>
(1) Turn on the power switch of the outdoor unit.
(2) With the Bits 1 and 2 of SW12 set to off, short-circuit the pins of CN30.
(3) Disconnect the connectors of PMV1 and 2 from the I/F P.C. board.
(4) With the Bits 1 and 2 of SW12 set to off and on, respectively, short-circuit the pins of CN30.
(5) Disconnect the connector of PMV4 from the I/F P.C. board
(6) Turn off the power switch of the outdoor unit.
Note: Steps (4) and (5) are not required for MMY-MAP0724HT6UL.
<Refrigerant charging>
Inject the same amount of refrigerant as the recovered residual refrigerant via the charging port of the liquid-side
service valve.