Check code
Location
of
detection
Description
System
status
Check code detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
E31 E31
I/F IPDU
communication
trouble
All stop Communication is disrupted
between IPDUs (P.C.
boards) in inverter box.
Check wiring and
connectors involved in
communication between
IPDU-I/F P.C. board for
bad contact or broken wire.
Check for trouble in
outdoor P.C. board (I/F,
A3-IPDU or Fan IPDU).
Check for external noise.
F01
Indoor
unit
Indoor TCJ
sensor trouble
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TCJ
sensor connector and
wiring.
Check resistance
characteristics of TCJ
sensor.
Check for trouble in indoor
P.C. board.
F02
Indoor
unit
Indoor TC2
sensor trouble
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TC2
sensor connector and
wiring.
Check resistance
characteristics of TC2
sensor.
Check for trouble in indoor
P.C. board.
F03
Indoor
unit
Indoor TC1
sensor trouble
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TC1
sensor connector and
wiring.
Check resistance
characteristics of TC1
sensor.
Check for trouble in indoor
P.C. board.
F04 F04
I/F TD1 sensor
trouble
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TD1
sensor connector.
Check resistance
characteristics of TD1
sensor.
Check for trouble in outdoor
P.C. board (I/F).
F05 F05
I/F TD2 sensor
trouble
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TD2
sensor connector.
Check resistance
characteristics of TD2
sensor.
Check for trouble in outdoor
P.C. board (I/F).
F06 F06
01: TE1 sensor trouble
02: TE2 sensor trouble
I/F TE1/TE2
sensor trouble
All stop
Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TE1/
TE2 sensor connectors.
Check resistance
characteristics of TE1/TE2
sensors.
Check for trouble in outdoor
P.C. board (I/F).
F07 F07
I/F
TL1
sensor trouble
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TL1
sensor connector.
Check resistance
characteristics of TL1
sensor.
Check for trouble in outdoor
P.C. board (I/F).
01: TL1 sensor trouble
Communication
trouble between
MCU and Sub
MCU
All stop
Communication between
MCU and Sub MCU stopped.
Operation of power supply
reset (OFF for 60 seconds
or more)
Outdoor I/F PC board
trouble check
80
1 2 1
01
02
03
08
09
0A
0B
A3-IPDU Fan-IPDU
150