14-1-5. Fan-IPDU P.C. Board (MCC-1610) Replacement Procedure
This board is commonly installed in different models before shipment. Set the DIP switch (SW800) setting of the
service board to the switch setting before replacement.
Replacement steps:
(1) Turn off the power supply of the outdoor unit and allow at least 5 minutes for the capacitor to discharge.
Check the light of LED(D690) turned off.
(2) Remove all the connectors and the Faston and screw terminals() connected to the FAN IPDU.
(Remove the connectors and Faston terminals by pulling the connector body. Do not pull the wire).
(3) Remove all five screws() which secures the FAN IPDU to the Heat sink.
(These screws are to be re-used after procedure.)
(4) Remove the Fan IPDU from the four PCB Mounts ().
(5) Confirm that no dirt or damage is on the sub heat sink. As it can reduce the heat transfer efficiency, and cause a
breakdown.
PCB Mounts
Faston terminal
BLACK lead wire
Screw
Faston terminal
WHITE lead wire
FAN IPDU
(MCC-1610)
Remove the PCB
IC701
Push this part to
the direction of the
arrow. And remove
the PCB.
MMY-MAP0726FT2P-UL
FAN-IPDU
Faston terminal
RED lead wire
Sub Heat Sink
Heat Sink
Power Supply
Input CN500
DB510
Q590
DB511
MCC-1610 (43T6V776)
Jumper for address setting
LED(D690)