CAUTION
In the case of the priority indoor unit mode, it is necessary to set up the specific indoor unit chosen for priority operation
(a single unit only).
(1) Outdoor unit setup method (header unit)
SW11
Operation
Bit 1 Bit 2
OFF OFF Priority heating (factory default)
ON OFF Priority cooling
OFF ON
Priority operation based on No. of units in operation (priority given to the operation mode with the
largest share of units in operation)
ON ON
Priority indoor unit (priority given to the operation mode of the specific indoor unit set up for priority
operation)
7-1-2. Priority Operation Mode Setting
Purpose/characteristics
This function allows switching between priority cooling and priority heating.
Four patterns of priority operation mode setting are available as shown in the table below. Select a suitable priority
mode according to the needs of the customer.