14-1- 4. Comp-IPDU P.C. Board (MCC-1683) Replacement Procedure
This board is commonly installed in different models before shipment. Set the DIP switch (SW800) setting of the
service board to the switch setting before replacement.
Replacement Steps:
(1) Turn off the power supply of the outdoor unit and allow at least 5 minutes for the capacitor to discharge.
Before going to Step (2), Check the light of LED(D800) turned off.
(2) Remove all the connectors and the Faston and screw terminals() connected to the Compressor IPDU.
(Remove the connectors by pulling the connector body. Do not pull the wire).
(3) Remove all the six screws() which secures the Compressor IPDU to the Heat sink.
(These screws are to be re-used after procedure.)
(4) Remove the Compressor IPDU from the four spacers () by pinching the top of the spacers by round-nose pliers.
Screw (M4x2)
Compressor IPDU
( 43T6V833)
Compressor IPDU
(MCC-1683
WHITE lead wire
BLACK lead wire
Reactor lead wire
BLACK lead wire
WHITE lead wire
RED lead wire
Screw (M3x2)
Spacer
SW800
MMY-MAP0726FT2P-UL
Pinch this part by
round-nose pliers for
removing the PCB.
(4 are in packed in this
service assembly)
LED(D800)
Screw (M4x2)