Check code
Location
of
detection
Description System status
Check code detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
H07 H07
I/F Low oil level
protection
All stop Operating compressor
detects continuous state of
low oil level for about 2 hours.
<All outdoor units in
corresponding line to be
checked>
Check balance pipe
service valve to confirm full
opening.
Check connection and
installation of TK1,
TK2, TK4, and TK5
sensors.
Check resistance
characteristics of TK1,
TK2, TK4, and TK5
sensors.
Check for gas or oil leak in
same line.
Check for refrigerant
problem inside
compressor casing.
Check SV3A, SV3B,
SV3C, SV3D valves for
trouble.
Check oil return circuit of
oil separator for clogging.
Check oil equalizing circuit
for clogging.
H08 H08
01: TK1 sensor trouble
02: TK2 sensor trouble
04: TK4 sensor trouble
05: TK5 sensor trouble
I/F
Trouble in
temperature
sensor for oil
level detection
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TK1
sensor connector.
Check resistance
characteristics of TK1
sensor.
Check for trouble in outdoor
P.C. board (I/F).
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TK2
sensor connector.
Check resistance
characteristics of TK2
sensor.
Check for trouble in outdoor
P.C. board (I/F).
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TK4
sensor connector.
Check resistance
characteristics of TK4
sensor.
Check for trouble in outdoor
P.C. board (I/F).
All stop Sensor resistance is infinity
or zero (open/short circuit).
Check connection of TK5
sensor connector.
Check resistance
characteristics of TK5
sensor.
Check for trouble in outdoor
P.C. board (I/F).
H15 H15
I/F TD2 sensor
miswiring
(incomplete
insertion)
All stop
Discharge temperature of
(TD2) does not increase
despite compressor 2 being
in operation.
Check installation of TD2
sensor.
Check connection of TD2
sensor connector and
wiring.
Check resistance
characteristics of TD2
sensor.
Check for trouble in outdoor
P.C. board (I/F).
153