Check code
Location
of
detection
Description
System
status
Check code
detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
P04 P04
01: Compressor 1 side
02: Compressor 2 side
IPDU Activation of high-
pressure SW
All stop High-pressure SW is
activated.
Check connection of high-
pressure SW connector.
Check for trouble in PD
pressure sensor.
Check outdoor service
valves (gas side, liquid side)
to confirm full opening.
Check for trouble in outdoor
fan.
Check for trouble in outdoor
fan motor.
Check outdoor PMVs (PMV1,
3) for clogging.
Check indoor/outdoor heat
exchangers for clogging.
Check for short-circuiting of
outdoor suction/discharge air
flows.
Check SV2 circuit for
clogging.
Check for trouble in outdoor
P.C. board (I/F).
Check for trouble in indoor
fan system (possible cause
of air flow reduction).
Check opening status of
indoor PMV.
Check indoor-outdoor
communication line for wiring
trouble.
Check for faulty operation of
check valve in discharge
pipe convergent section.
Check gas balancing SV4
valve circuit.
Check SV5 valve circuit.
Check for refrigerant
overcharging.
P05 P05
I/F All stop
Inverter DC
voltage is too high
(overvoltage) or
too low
(undervoltage).
AC power can not
be detected.
01: Compressor 1 side
02: Compressor 2 side
Inverter DC voltage
(Vdc) trouble
(compressor)
AC detection circuit
trouble
P07 P07
01: Compressor 1 side
02: Compressor 2 side
IPDU
I/F
Heat sink
overheating trouble
All stop
Temperature sensor
built into IPM (TH) is
overheated.
Check power supply voltage.
Check outdoor fan system
trouble.
Check heat sink cooling duct
for clogging.
Check IPM and heat sink for
thermal performance for faulty
installation.
(e.g. mounting screws and
thermal conductivity)
Check for trouble in A3-
IPDU.(faulty IPM built-in
temperature sensor (TH))
P10 P10
Detected indoor address Indoor
unit
Indoor overflow trouble
All stop Float switch
operates.
Float switch circuit
is open-circuited
or disconnected at
connector.
Check float switch connector.
Check operation of drain
pump.
Check drain pump circuit.
Check drain pipe for clogging.
Check for trouble in indoor
P.C. board.
P12
Indoor
unit
Indoor fan motor trouble
Stop of
corresponding
unit
Motor speed
measurements
continuously
deviate from target
value.
Overcurrent
protection is
activated.
Check connection of fan
connector and wiring.
Check for trouble in fan
motor.
Check for trouble in indoor
P.C. board.
Check impact of outside
air treatment (OA).
Check for trouble in
outdoor
P.C. board (A3-IPDU).
Check wiring of
outdoor power supply.