(2)Display of Outdoor Unit Information (Displayed on Each Outdoor Unit)
liated yalpsiD30WS20WS10WS
1
1
1
Outdoor unit No.: [U1] to [U3]
A
Check code data
B Check code (only latest one displayed)
If there is no check code, [– – –] is displayed.
If there is sub-code, check code [
] and sub-code [– ] are displayed
alternately, for 3 seconds and 1 second, respectively.
2
A
B–
3
Operation mode A Stop [… …]
Normal cooling: [… C], Normal heating: [… H], Normal defrosting: [… J]
B–
4
Outdoor unit capacity
A
6 ton : [... … 6.0t.], 8 ton : [... … 8.0t.], 10 ton : [… 10.0 t.],
12 ton : [... 12.0 t.], 14 ton : [...14.0 t.]
B
[…ton]
5
Compressor operation command * Operation data of each compressor is displayed in turn in 2 second intervals.
Normal: Compressor speed (rps) is displayed in decimal format.
7-segment display (A/B): [C1. ... ... ... ] [ ... ∗ ∗ ∗
, ] [C2. ... ... ... ] [ ... ∗ ∗ ∗
, ]
<SW04> push SW function: Switches to display of operating current (decimal value).
7-segment display (A/B): [i1. ] [i2. ]
Pressing of <SW05> restores normal display.
6
Outdoor fan mode A [FP]
B Mode 0 to 63: [… 0] to [63]
7
Compressor backup A [C.b.]
B
Displays compressor backup setting status
Normal: [… … …]
Compressor No. 1 backup: [1 … …]
Compressor No. 2 backup: [… 1 …]
8
A
B–
<SW04> push SW function: Fan operation at outdoor unit with trouble. 7-segment display section A: [E.1]
<SW04 + SW05> push SW function: Fan operation at outdoor unit without trouble. 7-segment display section A: [E.0]
<SW05> push SW function: Fan operation function check mode is cancelled.
197
Control valve output data Displays control output status of solenoid valve A B
4-way valve: ON H. 1 … … …
4-way valve: OFF H. 0 … … …
SV2: ON / SV5: OFF / SV52: ON / SV6: OFF 2. 1 0 1 0
SV2: OFF / SV5: ON / SV52: OFF / SV6: OFF 2. 0 1 0 0
SV2: OFF / SV5: OFF / SV52: OFF / SV6: ON 2. 0 0 0 1
SV3A: ON / SV3B: OFF / SV3C: OFF / SV3D: OFF 3. 1 0 0 0
SV3A: OFF / SV3B: ON / SV3C: OFF / SV3D: OFF 3. 0 1 0 0
SV3A: OFF / SV3B: OFF / SV3C: ON / SV3D: OFF 3. 0 0 1 0
SV3A: OFF / SV3B: OFF / SV3C: OFF / SV3D: ON 3. 0 0 0 1
SV41: ON / SV42: OFF 4.
...
SV41: OFF / SV42: ON 4.
...
SV41: OFF / SV42: OFF 4.
...
SV11A,B: ON / SV12: ON / SV14: ON / SV15: OFF
A. 1
1 1 0
SV11A,B: OFF / SV12: OFF / SV14: OFF / SV15: ON
A. 0
0 0 1
14
PMV1/PMV3 opening Displays opening data in decimal format
"Press <SW04>, then PMV1 display switches to
PMV3 display".
* * * * .P
15 PMV4 opening Displays opening data in decimal format … * * * .P
Oil level judgment
Normal A [ o L.]
B Initial display: [… … …], Oil level judgment result: [L … …]
Displayed letters #, * and $ represent judgment results for compressor Nos.
1 and 2, respectively ("0" for normal and "1" or "2" for low level).
<SW04> push SW function: Displays low level confirmed judgment result of each compressor.
* A [L d.]Pressing of <SW05>
restores normal display. B Compressor No.1 low level being confirmed: [L … …]
Compressor No.2 low level being confirmed: [… L …]
<SW15> push SW function: Switch to the data display of insufficient confirmation integration timer for 2 minutes
A [t …]
B
Insufficient confirmation integration timer : [1 2 0] (Ex: for 120 minutes)
16
9
10
11
12
13
PMV1
PMV3
* *
* * .P