EasyManua.ls Logo

Toshiba MMY-MAP0726FT2P-UL - Page 201

Toshiba MMY-MAP0726FT2P-UL
287 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B
4
Indoor BUS communication signal
receiving status
Upon receiving signal: [... ... 1], Other times: [... ... ...]
B5 Indoor check code No check code: [– – –]
B
6
Indoor capacity
... 0.6, ... 0.8, ... 1.0, ... 1.2, ... 1.5, ... 1.7, ... 2.0, ... 2.2, ...
2.5, ... 3.0, ... 4.0, ... 4.5, ... 6.0, ... 8.0, 12.0, 14.0, 16.0
8 Indoor PMV opening data Displayed in decimal format
9
1~4
1~16
Indoor TA / TRA opening data Displayed in decimal format
11~14 Indoor TSA opening data
Displayed in decimal format
10 Displayed in decimal format
1~4 Indoor TF / TFA opening data
11~14 Indoor TOA opening data
Displayed in decimal format
B11 Indoor TCJ opening data Displayed in decimal format
B12 Displayed in decimal format
B13
1~4 Indoor TC1 opening data
Indoor TC2 opening data
Displayed in decimal format
B
7
Indoor request command
(S code, operation mode)
[ #. ...
]
# represents mode:
COOL: [C. ...
], HEAT: [H. ...
]
FAN: [F. ...
], OFF: [S. ...
]
represents S code: [#. ... 0] to [#. ... F]
SW01 SW02 SW03 Display detail
SW02
1~16
SW03
1
11
2
12
3
13
Indoor address
SW02 setting number
SW02 setting number +16
SW02 setting number +32
7-segment display section A
[01]~[16]
[17]~[32]
[33]~[48]
(5) Display of Indoor Unit Information (Displayed on Header Unit Only)
Note: Indoor address No. is selected by setting SW02 and SW03 and displayed on 7-segment display, section A.
(6) Display of Outdoor EEPROM Writing Check Code (Displayed on Header Unit Only)
* The latest code written in the EEPROM of each outdoor unit is displayed.
(This function is used to check the code after the resetting of the power supply.)
To display the code, push SW04 and hold for at least 5 seconds after setting SW01 to 03 as shown in the
table below.
7-Segment Display
SW01 SW02 SW03 Indoor address 7-segment display section A
1 E. 1.
∗∗∗
Latest check code of header unit (U1)
1216 E. 2.
∗∗∗
Latest check code of follower unit No. 1 (U2)
3 E. 3.
∗∗∗
Latest check code of follower unit No. 2 (U3)
Section A
Section B
D600 D601 D602 D603 D604
Set SW01/SW02/SW03 to [1/1/16] and push SW04 and hold for at least 5 seconds. The latest code of the
header unit (U1) will be displayed.
If the setting of SW02 is changed, the latest code of a follow unit (U2-U3) will be displayed.
4
14
SW02 setting number +48
[49]~[64]
200
B
B
B